148
P4-05
P4-06
输出频率
E2-0X = 49
运转指令
OFF
ON
ON(
闭
)
OFF(
开
)
Figure 6.60.2 brake control schematic
Note1. Brake control is set to the terminal of the once closed, to simultaneously meet the "inverter
operation command to OFF" and "Output frequency
≤
P4-06", the terminal will disconnect
100 to 149 : 0 to 49 with Inverse Output
Inverted output of the selected multi-function contact output. By 1 □□ after 2 to select
reverse output.
Example : 106 = "6 (base interdiction in)" Reverse output
E2- 04 Retain
E2- 05 Watt Hour Output Unit
Selects the output unit for the terminal assigned to E2-00 or E2-03=37 for one pulse signal.
This output function provides a watt hour meter or a PLC input by a 200ms pulse signal.
No.
Name
Setting Range
Default
E2-05
Watt Hour Output Unit
0
∶
0.1 kWh units
1
∶
1 kWh units
2
∶
10 kWh units
3
∶
100 kWh units
4
∶
1000 kWh units
0
Note:
1. When a power output is negative(i.e. regeneration), it does not subtract from the total watt hours.
2. The drive keeps track of the watt hours only when the control circuit is powered. The value is reset once the
power supply is cut off.
Frequency Reference
Run Command