µSDM-1RD / µSDM-1 / µSDM-1E IOM
Mechanical Installation
426006-2304-013-B1
Lightscape Networks Ltd. Proprietary
4-9
4. Place the mounting bracket with the unit on the rack mounting shelf as
4-6. Attach the mounting bracket to the shelf by means of a
single screw at the base of the mounting bracket.
5. Repeat Step 4 for additional units on the shelf. Up to 3 or 4 units can be
placed on a single shelf, depending on the model.
6. Attach the shelf to the rack as shown in Figure
7. Close the protective door.
Equipment Grounding Requirements
Equipment should be grounded via the mounting brackets secured to the rack’s rails.
The sides of the mounting brackets facing the rails and the equipment must be
unpainted and electrically conductive. The conductivity of the mounting brackets to
the equipment frames (sub-racks) must be verified (below 0.2
Ω
).
Figure
4-6: Attaching the mounting bracket for vertical rack mounting
Содержание mSDM-1
Страница 16: ...Introduction SDM 1RD SDM 1 SDM 1E IOM 1 6 Lightscape Networks Ltd Proprietary 426006 2304 013 B1...
Страница 26: ...Product Description SDM 1RD SDM 1 SDM 1E IOM 2 10 Lightscape Networks Ltd Proprietary 426006 2304 013 B1...
Страница 100: ...Acceptance and Commissioning SDM 1RD SDM 1 SDM 1E IOM 7 6 Lightscape Networks Ltd Proprietary 426006 2304 013 B1...
Страница 109: ...426006 2304 013 B1 Lightscape Networks Ltd Proprietary B 1 Packing List A typical SDM 1 packing list...
Страница 110: ...Packing List SDM 1RD SDM 1 SDM 1E IOM B 2 Lightscape Networks Ltd Proprietary 426006 2304 013 B1...
Страница 122: ...Connector Pin Outs SDM 1RD SDM 1 SDM 1E IOM C 12 Lightscape Networks Ltd Proprietary 426006 2304 013 B1...
Страница 132: ...Rack Installation Guidelines SDM 1RD SDM 1 SDM 1E IOM E 4 Lightscape Networks Ltd Proprietary 426006 2304 013 B1...