400 Legrand PDU User Guide
<hy_value> is a numeric value that is assigned to the hysteresis for the specified inlet pole sensor. See
"To De-assert" and Deassertion Hysteresis
(on page 513).
<as_value> is a number in samples that is assigned to the assertion timeout for the specified inlet pole
sensor. See
"To Assert" and Assertion Timeout
(on page 511).
Additional sensors supported by Legrand PDUs:
The CLI command(s) listed above can be also applied to the following sensors. Note that the measurement
unit of current values in CLI is
A
, not mA.
Sensor type
Description
peakCurrent Peak
current
sensor
reactivePower
Reactive power sensor
displacementPowerFa
ctor
Displacement power factor sensor
phaseAngle
Inlet phase angle sensor
Commands for Overcurrent Protector Sensors
A sensor configuration command for overcurrent protectors begins with
sensor ocp
.
You can configure various overcurrent protector threshold settings at a time by combining multiple
commands. See
Multi-Command Syntax
(on page 408).
Set the Upper Critical threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an overcurrent protector: