Janu
ary 201
9
314 Legrand PDU User Guide
Load Shedding Settings
This section applies to outlet-switching capable models only.
This command shows the load shedding settings.
#
show loadshedding
Displayed information:
The load shedding state is displayed along with non-critical outlets.
Note: The load shedding mode is associated with critical and non-critical outlets. To specify critical and
non-critical outlets through CLI, see
Specifying Non-Critical Outlets
(on page 321).
Serial Port Settings
This command shows the baud rate setting of the serial port labeled CONSOLE on the Legrand PDU.
#
show serial
EnergyWise Settings
This command shows the Legrand PDU device's current configuration for Cisco
®
EnergyWise.
#
show energywise
Event Log
The command used to show the event log begins with
show eventlog
. You can add either the
limit
or
class
parameters or both to show specific events.
Show the last 30 entries:
#
show eventlog
Show a specific number of last entries in the event log:
#
show eventlog limit <n>
Show a specific type of events only:
#
show eventlog class <event_type>
Show a specific number of last entries associated with a specific type of events only:
#
show eventlog limit <n> class <event_type>
Variables:
<n> is one of the options:
all
or a number.
Option
Description
all
Displays all entries in the event log.
Содержание 1U
Страница 1: ...Legrand PDU User Guide Xerus Firmware v3 5 0 ...
Страница 2: ...Copyright 2019 Legrand Inc LG 0B v3 5 0 E January 2019 255 80 0054 00 ...
Страница 53: ...January 2019 Legrand PDU User Guide 53 ...
Страница 77: ...January 2019 Legrand PDU User Guide 77 4 Press to show the Network Cascading page ...