Legrand PDU User Guide 321
config:#
pdu outletSequenceDelay <outlet1>:<delay1>;<outlet2>:<delay2>;
<outlet3>:<delay3>;...
Separate outlet numbers and their delay settings with a colon. Outlets followed by delays are separated with
a semicolon.
Variables:
<outlet1>, <outlet2>, <outlet3> and the like are individual outlet numbers or a range of outlets using a
dash. For example,
3-8
represents outlets 3 to 8.
<delay1>, <delay2>, <delay3> and the like are the delay time in seconds.
Setting the PDU-Defined Default Outlet State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of all outlets after powering up the PDU.
config:#
pdu outletStateOnDeviceStartup <option>
Variables:
<option> is one of the options:
off
,
on
or
lastKnownState
.
Option
Description
off
Switches OFF all outlets when the Legrand PDU
powers up.
on
Switches ON all outlets when the Legrand PDU
powers up.
lastKnownState Restores all outlets to the previous status before
powering down the Legrand PDU when the PDU
powers up again.
Setting the PDU-Defined Cycling Power-Off Period
This section applies to outlet-switching capable models only.
This command sets the power-off period of the power cycling operation for all outlets.
config:#
pdu cyclingPowerOffPeriod <timing>
Variables:
<timing> is the time of the cycling power-off period in seconds, which is an integer between 0 and 3600,
or
pduDefined
for following the PDU-defined timing.