176 Legrand PDU User Guide
Configuring SNMP Settings
You can enable or disable SNMP communication between an SNMP manager and the Legrand PDU.
Enabling SNMP communication allows the manager to retrieve and even control the power status of each
outlet.
Besides, you may need to configure the SNMP destination(s) if the built-in "System SNMP Notification Rule"
is enabled and the SNMP destination has not been set yet. See
Event Rules and Actions
(on page 199).
To configure SNMP communication:
1. Choose Device Settings > Network Services > SNMP.
2. Enable or disable "SNMP v1 / v2c" and/or "SNMP v3" by clicking the corresponding checkbox.
The SNMP v1/v2c read-only access is enabled by default. The default 'Read community string' is
"public."
To enable read-write access, type the 'Write community string.' Usually the string is "private."
3. Enter the MIB-II system group information, if applicable.
sysContact - the contact person in charge of the system
sysName - the name assigned to the system
sysLocation - the location of the system
4. To configure SNMP notifications: