Janu
ary 201
9
Legrand PDU User Guide 69
Check the outlet state shown on the LCD display -- red or green circles.
Check the outlet LED. A green LED indicates that the outlet is turned off, and a red LED indicates
that the outlet is turned on.
8. To return to the Main Menu, press
several times until the Main Menu is shown.
Outlet Groups
This outlet-related section applies to Legrand Switched PDUs only.
You can do the following on the front panel display:
Show each outlet group's information, including each member outlet of a group.
Turn on, off or power cycle an individual outlet group if your Legrand PDU is outlet-switching capable. To
do this, you must first enable the front panel outlet control function. See
Front Panel Settings
(on page
247).
Showing an Outlet Group's Information
If any outlet group has been created, the front panel then shows a list of these groups and their status. See
Creating an Outlet Group
(on page 118).
Control buttons that can be used and the system time are shown at the bottom of the LCD display.
To show an outlet group's information:
1. Press
or
to select "Outlet Groups" in the Main Menu, and press
.
2. The LCD display shows a list of outlet groups with the information below:
The total number of outlets in the group
Power states which are indicated by the colors of circles
The total number of outlets that are turned ON in the group
The currently-selected outlet group's number and total of outlet groups are indicated in the top-right
corner of the display, such as "1/4" in the above diagram.
A red circle indicates that all outlets of the group are powered on.
A green circle indicates that all outlets of the group are powered off.
A half-red half-green circle indicates some outlets are powered on while the others of the group are
powered off.
3. Press
or
to select an outlet group, and press
.
If the desired outlet group is not visible, press
or
to scroll up or down.