Legrand PDU User Guide 235
3. Select "Any sub-event" to include all events related to all sensors of this inlet and all thresholds, such as
current, voltage, upper critical threshold, upper warning threshold, lower critical threshold, lower warning
threshold, and so on.
4. To make the Legrand PDU send SNMP notifications, select "System SNMP Notification Action" in the
'Available actions' box.
Note: The SNMP notifications may be SNMP v2c or SNMP v3 traps/informs, depending on the settings
for the System SNMP Notification Action. See
Enabling and Configuring SNMP
(on page 288).
Then the SNMP notifications are sent when:
Any numeric sensor's reading enters the warning or critical range.
Any sensor reading or state returns to normal.
Any sensor becomes unavailable.
The active energy sensor is reset.
For example, when the Inlet I1's voltage exceeds the upper warning threshold, the SNMP notifications
are sent, and when the voltage drops below the upper warning threshold, the SNMP notifications are
sent again.
Sample Environmental-Sensor-Level Event Rule
This section applies to outlet-switching capable models only.
In this example, we want Legrand PDU to activate the load shedding function when a contact closure sensor
enters the alarmed state. This event rule requires creating a new action before creating the rule.
Step 1: create a new action for activating the load shedding
1. Choose Device Settings > Event Rules >
.
2. In this illustration, assign the name "Activate Load Shedding" to the new action.
3. In the Action field, select "Change load shedding state."