222 Legrand PDU User Guide
Switch Outlet Group
The "Switch outlet group" action is available only when your Legrand PDU is outlet-switching capable. This
action turns on, off or power cycles a specific outlet group.
Operation:
1. Choose Device Settings > Event Rules >
.
2. Select "Switch outlet group" from the Action list.
3. To specify the outlet group where this action will be applied, select it from the 'Group to switch' list.
4. In the Operation field, select an operation for the selected outlet group.
Turn on all outlets in group: Turns on the selected outlet group.
Turn off all outlets in group: Turns off the selected outlet group.
Cycle all outlets in group: Cycles power to the selected outlet group.
Switch Outlets
The "Switch outlets" action is available only when your Legrand PDU is outlet-switching capable. This action
turns on, off or power cycles a specific outlet.
Operation:
1. Choose Device Settings > Event Rules >
.
2. Select "Switch outlets" from the Action list.
3. In the Operation field, select an operation for the selected outlet(s).
Turn Outlet On: Turns on the selected outlet(s).
Turn Outlet Off: Turns off the selected outlet(s).
Cycle Outlet: Cycles power to the selected outlet(s).
4. To specify the outlet(s) where this action will be applied, select them one by one from the Available
Outlets list.
To add all outlets, click Select All.
5. To remove any outlets from the Selected Outlets field, click that outlet's
.
To remove all outlets, click Deselect All.
6. If "Turn Outlet On" or "Cycle Outlet" is selected in step 3, you can choose to select the "Use sequence
order and delays" checkbox so that all selected outlets will follow the power-on sequence defined on the
page of
Outlets
(on page 107).
Switch Peripheral Actuator
If you have any actuator connected to the Legrand PDU, you can set up the Legrand PDU so it automatically
turns on or off the system controlled by the actuator when a specific event occurs.
Note: For information on connecting actuators, see
DX Sensor Packages
(on page 42) or
DX2 Sensor
Packages
(on page 41).
Operation:
1. Choose Device Settings > Event Rules >
.
2. Select "Switch peripheral actuator" from the Action list.
3. In the Operation field, select an operation for the selected actuator(s).
Turn On: Turns on the selected actuator(s).
Turn Off: Turns off the selected actuator(s).
4. To select the actuator(s) where this action will be applied, select them one by one from the Available
Actuators list.
To add all actuators, click Select All.