Legrand PDU User Guide 407
<succ_number> is the number of successful pings for declaring the monitored device "Reachable." Valid
range is 0 to 200.
<fail_number> is the number of consecutive unsuccessful pings for declaring the monitored device
"Unreachable." Valid range is 1 to 100.
<succ_wait> is the wait time to send the next ping after a successful ping. Valid range is 5 to 600
(seconds).
<fail_wait> is the wait time to send the next ping after a unsuccessful ping. Valid range is 3 to 600
(seconds).
<resume> is the wait time before the Legrand PDU resumes pinging after declaring the monitored device
"Unreachable." Valid range is 5 to 120 (seconds).
<disable_count> is the number of consecutive "Unreachable" declarations before the Legrand PDU
disables the ping monitoring feature for the monitored device and returns to the "Waiting for reliable
connection" state. Valid range is 1 to 100 or
unlimited
.
Example - Server Settings Changed
The following command modifies several ping monitoring settings for the second server in the server
reachability list.
config:#
serverReachability modify 2 numberOfSuccessfulPingsToEnable 10
numberOfUnsuccessfulPingsForFailure 8
waitTimeAfterSuccessfulPing 30
EnergyWise Configuration Commands
An EnergyWise configuration command begins with
energywise
.
Enabling or Disabling EnergyWise
This command syntax determines whether the Cisco
®
EnergyWise endpoint implemented on the Legrand
PDU is enabled.
config:#
energywise enabled <option>
Variables:
<option> is one of the options:
true
or
false
.
Option
Description
true
The Cisco EnergyWise feature is enabled.
false
The Cisco EnergyWise feature is disabled.