Legrand PDU User Guide 137
Sensor/Actuator States
An environmental sensor or actuator shows its real-time state after being managed.
Available sensor states depend on the sensor type -- numeric or state sensors. For example, a contact
closure sensor is a state sensor so it switches between three states only --
unavailable
,
alarmed
and
normal
.
Sensors will be highlighted in yellow or red when they enter abnormal states. See
Yellow- or
Red-Highlighted Sensors
(on page 135).
An actuator's state is marked in red when it is turned on.
Managed sensor states:
In the following table, "R" represents any numeric sensor's reading. The symbol <= means "smaller than" or
"equal to."
State
Description
normal
For numeric sensors, it means the
readings are within the normal range.
For state sensors, it means they enter the
normal state.
below lower critical
"R" < Lower Critical threshold
below lower warning
Lower Critical threshold <= "R" < Lower
Warning threshold
above upper warning
Upper Warning threshold < "R" <= Upper
Critical threshold
above upper critical
Upper Critical threshold < "R"
alarmed
The state sensor enters the abnormal state.
unavailable
The communication with the managed
sensor is lost.
-- OR --
DPX2, DPX3, DX or DX2 sensor packages
are upgrading their sensor firmware.
Note that for a contact closure sensor, the normal state depends on the normal setting you have configured.
Refer to the Environmental Sensors and Actuators Guide (or Online Help) for detailed information, which is
available on Raritan's
Support page
(
Managed actuator states:
State
Description
on
The actuator is turned on.
off
The actuator is turned off.
unavailable
The communication with the managed
actuator is lost.
-- OR --
DX sensor packages are upgrading their
sensor firmware.
Содержание 1U
Страница 1: ...Legrand PDU User Guide Xerus Firmware v3 5 0 ...
Страница 2: ...Copyright 2019 Legrand Inc LG 0B v3 5 0 E January 2019 255 80 0054 00 ...
Страница 53: ...January 2019 Legrand PDU User Guide 53 ...
Страница 77: ...January 2019 Legrand PDU User Guide 77 4 Press to show the Network Cascading page ...