INS-16
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
The connection of drain hose is on right side of each Indoor Unit only. If it is necessary to extend drain
hose, use a pipe in semirigid plastic (PVC) of VP20 type, to buy separately. Connect the extension by
using a special fitting (refer to the Figure below).
(9) Wiring
1. Indoor Units. Power lines and signal cable (min. section of 1.5mm
2
for all Models), prewired-up on
each Indoor Unit and provided of plug, must pass from Indoor Unit to Outdoor Unit, by starting from Indoor
Unit’s back and getting to specific connector (Unit “A”, “B”, “C”, “D”) on Outdoor Unit. If it is needed to
increase wiring standard length (6 metres), always use cables in accordance with to law only.
2. Terminal block can be reached by removing electric box’s protection cover, on Indoor Unit’s right side.
3. Always fix cables on screw terminal blocks firmly, and always use the special wire clamps on Indoor
Units to avoid that any traction on cables may be sent to terminal blocks’ contacts.
4. If protection fuse is broken, replace it by a fuse which is equivalent to original one.
5. Outdoor Unit. Power supply line must be for system only, that is it must not be shared with other
appliances. A circuit breaker must be installed - with suitable calibration to the system’s power input -
which simultaneously interrupts all contacts; in opening position, min. distance between contacts must
be of 3 mm. Moreover, the installation of an earth breaker is required, specific for Inverter appliances.
NO
NO
NO
Higher than specified
Trap
The drain hose tip is in water
Flexible drain hose
Adhesive
Vinyl tape (narrow)
Drain hose’s extension
CORRECT
Wire clamp
Terminal blocks
Passage of wiring, connections of terminals and use of wire clamps
Grommet terminals
WRONG
L
N
S
L
N
S