(1) Selection of installation site for HTFU (206, 266, 356, 536) X Indoor Units
n
Install Indoor Units in a place having the following requirements:
- The fixing surface must be able to support the Unit’s weight.
- Material features of wall must not cause vibrations.
- There must be no heating sources nor vapors near the Unit.
- There must be no obstacles on the air inlet and outlet.
- Spaces for maintenance and air circulation (inlet and outlet) must be assured.
- Indoor Unit must not be exposed to direct sunlight for a long time.
- Drain hose must be correctly installed, so as the condensate water can easily flow away.
- Laying of cables and refrigerant pipings towards outside must be easy.
- Air supplied by Indoor Unit must reach whole room.
n
Installation must be avoided in places where there are the following conditions (not exhaustive list):
- There are sources of electromagnetic noises (TV, radio, wireless appliances) or fluorescent lamps.
- Kitchens with high humidity and vapors/oil sprinkles.
- There are considerable sudden changes in power supply voltage.
n
Min. spaces indicated on the Figure below must be respected:
Air inlet
Air outlet
Air outlet
> 2300
A
≥
280
Floor
> 1000
> 1000
> 1000
> 1000
CAUTION
Install Indoor Unit in the false ceiling, by threaded bars, at more than 2.3m high from the floor.
Unit: mm