OUT-50
DUAL, TRIPLE, POKER DC Inverter : 3. Outdoor Unitis & Troubleshooting
Multi Liberty
DC Inverter
P 5
Operation mode in conflict with operation mode of other Indoor Units
Protection Code on Indoor Unit
Outline of Protection function
• Troubleshooting for Protection Codes shown on Display of Multi Liberty HKEU X Indoor Unit
On Indoor Units of the same system, have operation modes not compatible
among them been set (see the Table below)?
On the Indoor Units of the same system, operation modes must be compatible
among them (see the Table below): correct the setting.
YES
Cooling
Cooling
Heating
Fan
OFF
Heating
Fan
OFF
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
Table of compatibility between Indoor Units’ operation modes: