INS-79
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
Indoor Unit “A”, “B”, “C”, or “D”
1 2(N) S
JX1 Terminal block
Yellow / Green
Connection of LED Display and IR Receiver
“PLUG” (= Connector)
for Outdoor Unit
CN3
CN11
CN13
CN2
CN9
CN4
Indoor Unit’s PCB
LED Display & IR Receiver
CN1
XS6
XP6
Connector
Standard lenght of cable: 6m
SW1 SW2
CN6
CN10
CN14
S
CN7
MANUAL
OPERATION TIMER DEF./FAN ALARM
HCKU 406 X2
Outdoor Units
Calibration of circuit breaker (A)
Section of power cables (mm
2
)
HCKU 536 X2
12A
2.5 mm
2
HCKU 606 X3
16A
4.0 mm
2
HCKU 806 X3
20A
6.0 mm
2
HCKU 706 X4
20A
6.0 mm
2
HCKU 816 X4
HCKU 1066 X4
20A
6.0 mm
2
32A
8.0 mm
2
32A
8.0 mm
2
• Power supply (on Outdoor Unit):
- 1-Phase, 220~240V, 50 Hz.
- Power source limitations: ±10% as regards rating value.
- Voltage at starting: 85% as regards rating value.
• Calibrations of circuit breakers and min. section of power cables:
Basic information on wiring for Multi Liberty DC Inverter systems