OUT-80
DUAL, TRIPLE, POKER DC Inverter : 3. Outdoor Unitis & Troubleshooting
Multi Liberty
DC Inverter
Error Code on Outdoor Unit
Outline of malfunction
E 1
Malfunction of temperature sensor, Gas side, on Indoor Unit “A”
Error Code on Outdoor Unit
Outline of malfunction
E 2
Malfunction of temperature sensor, Gas side, on Indoor Unit “B”
Is Gas side temperature sensor on Indoor Unit “A” properly connected?
Are sensor wirings OK?
YES
NO
Measure the sensor resistance. Considering temperature, does resistance value
correspond to the features indicated in R-T tables?
NO
YES
Replace wirings/connector of
sensor.
Replace Gas side temperature sensor on
Indoor Unit “A”.
Replace Outdoor Unit’s main
PCB.
Is Gas side temperature sensor on Indoor Unit “B” properly connected?
Are sensor wirings OK?
YES
NO
Measure sensor resistance. Considering temperature, does resistance value
correspond to the features indicated in R-T tables?
NO
YES
Replace wirings/connector of
sensor.
Replace Gas side temperature sensor on
Indoor Unit “B”.
Replace Outdoor Unit’s main
PCB.
• Troubleshooting flowchart, referred to Error Codes displayed on Outdoor Unit: