INS-24
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
(2) Transport of Indoor Unit
1. Decide the correct carry-in path.
2. Move this Unit as originally packaged as possible.
3. If the air conditioner is installed on a metal part of the building, it must be electrically insulated according
to the relevant electrical code.
4. If installing in a lonely building or at a high position where it is hot and humid with frequent thunderstorm,
lightning-protection equipment is necessary.
(3) Installation of Indoor Unit’s body
Case “A”. In case of existing false ceiling.
a) Please cut a quadrangular hole of 600 x 600mm
in the false ceiling, according to the shape of the
installation paper board (provided with the Indoor Unit).
m
The centre of the hole should be at the same
position of that of the air conditioner’s main body.
m
Determine the length and outlets of the connecting
pipes, drain pipe and cables.
m
To balance the ceiling and to avoid vibration, please
enforce the ceiling when necessary.
b) Please select the position of installation hooks for
wall anchors (Ø12mm, hook-ended, supplied with the
Indoor Unit), indicated on the installation paper board.
m
Drill 4 holes (Ø12mm), 50~55mm deep at the
selected positions on the ceiling. Then embed the
expansible hooks (fittings).
m
Face the concave side of the installation hooks
toward the expansible hooks. Determine the length of
the installation hooks from the height of ceiling, then
cut off the unnecessary part.
m
Standard length of suspension bars must be:
(210mm + L), where “L” is the part of threaded bar
that juts out as regards square brackets for Indoor
Unit’s suspending.
m
If the false ceiling is extremely high, please
determine the length of suspension bars
according to facts. If suspension bars are
extremely long, please connect reinforcement
67
422
28.5
650 (Panel)
611 (Distance between suspension bars)
600 (False ceiling’s hole)
580 (Unit’s body)
600
Bar
285
Panel
Unit’s body
Nuts
False ceiling
650 (Panel)
401 (Distance between suspension bars)
600 (False ceiling’s hole)
580 (Unit’s body)
Fig.1
Fig.2
H (f
alse ceiling’
s height)
Fig.3
Unit’s body
Ceiling