INS-25
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
brackets (Ø12mm) between each bar and contiguous bars, so as to make an external square structure.
c) Please adjust scrupulously Indoor Unit’s height, by intervention on lower hexangular nut of each
threaded bar, so as to ensure the best balance of Indoor Unit’s body - after Indoor Unit has been
suspended to bars by its square brackets.
m
Use the PVC transparent hose filled with water to check the horizontal adjustment of Indoor Unit’s
body. Position the hose as it is shown in the Figure below, or please use a spirit level.
m
If Indoor Unit is not perfectly horizontally positioned, the air conditioner may stop for a malfunction
due to the intervention of the float switch, or leakages of water due to non-intervention of float switch.
m
Please centre Indoor Unit’s body as regards 4 sides of hole cut in the false ceiling.
m
Indoor Unit’s suspension height must be such as the body’s lower part is about 10~12mm higher
than false ceiling’s lower side.
m
After Indoor Unit has been positioned perfectly horizontally, definitively tighten the nut and the lock
nut near each square bracket of Unit’s body.
Fig.5
CASE “B”. New built houses and false ceilings.
a) In case of new built house, the hook can be embedded in advance. But it should be strong enough
to bear the Indoor Unit and will not become loose because of concrete shrinking.
b) After installing the body, please fasten the installation paper board onto the air conditioner with the
provided 4 bolts (M5 x 16). In this way, it will be easy to determine the sizes and positions of the hole
opening on ceiling.
m
Please first guarantee the flatness and horizontal of false ceiling when installing it.
c) For following phases of installation, please refer to items b) & c) of previous Case “A”.
m
At the end of installation of Unit’s body, please remove installation paper board.
Fig.4
Spirit level
PVC transparent pipe
filled with water
Fig.6
Unit’s body
Centre of installation paper board
Holes (4) for
suspension bars
Installation paper board
Bolts (4) M5 x 16
(provided)
Fixing holes (4) for
installation paper board