OUT-44
DUAL, TRIPLE, POKER DC Inverter : 3. Outdoor Unitis & Troubleshooting
Multi Liberty
DC Inverter
NO
NO
YES
YES
NO
Are
the
connectors
of
temperature sensors T1 and T2,
and wirings of both sensors OK?
Replace one of both sensors
(T1, T2). Does Code “E6”
appear again?
Do R-T features of sensors
correspond to those that are
listed further on?
Replace Indoor Unit’s PCB.
YES
Replace Indoor Unit’s PCB.
The problem is solved.
Restore temperature
sensors’ connectors and
connect them again on
Indoor Unit’s PCB.
Error on Indoor Unit
Outline of malfunction
E 6
Malfunction of T1 sensor or T2 sensor on Indoor Unit
• Troubleshooting for Error Codes shown on Display on Multi Liberty HKEU X Indoor Units
Malfunction of temperature sensor T1 (indoor
temperature) or temperature sensor T2 (heat
exchanger’s temperature) on Indoor Unit.