INS-45
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
1 2(N) S
Terminal block JX1
HCKU 406 X2
Outdoor Units
Calibration of circuit breaker (A)
Section of power cables (mm
2
)
HCKU 536 X2
12A
2.5 mm
2
HCKU 606 X3
16A
4.0 mm
2
HCKU 806 X3
20A
6.0 mm
2
HCKU 706 X4
20A
6.0 mm
2
HCKU 816 X4
HCKU 1066 X4
20A
6.0 mm
2
32A
8.0 mm
2
32A
8.0 mm
2
Power supply
terminal block
Yellow / Green
• Power supply (on Outdoor Unit):
- 1-Phase, 220~240V, 50 Hz.
- Power source limitations: ±10% as regards rating value.
- Voltage at starting: 85% as regards rating value.
• Calibrations of circuit breakers and min. section of power cables:
Basic information on wiring for Multi Liberty DC Inverter systems
Outdoor Unit
1 2(N)
• Min. section of cables (prewiring-up = 6m) between each Indoor Unit and the Outdoor Unit:
- All Models → 1.5mm
2.
“PLUG” (= connector)
for Outdoor Unit
Indoor Unit “A”
Indoor Unit “B”
Indoor Unit “C”
Indoor Unit “D”
Indoor Unit “A”, “B”, “C”, or “D”