INS-68
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
Fig. 3.2.1
Unit: mm
Refrigerant
piping
connections
Air outlet
Air inlet plenum
VIEW A
>500mm
>100mm
2. Check of Indoor Unit after transport and following removal
1.
“Fragile”. Handle with care.
Do not turn packaging upside down to avoid damages to panels.
2.
Determine the easiest path for removing Indoor Unit to installation site.
3.
Keep Indoor Unit protected inside its original packaging till installation.
4.
During lifting of Indoor Unit, place special protective devices between slinging tie rods and Unit itself.
3. Installation of Indoor Unit
3.1 Selection of installation position
For installation of Indoor Unit, select a place having the following requirements:
●Suitable spaces for installation and maintenance must be available.
●Select a leveled fixing surface, which is strong enough to support Unit’s weight.
●Air outlet and inlet must be free. Air draft from outside must not interfere with Unit’s operation.
●Air supplied by Unit must be distributed inside the room uniformily.
●Laying of refrigerant pipings and drain hose must be easy.
●There must be no heating source near Unit.
Caution:
3.2 Fixing of Indoor Unit’s body
1. Installation of bolts with anchors (Ø10, 4 pieces) for Unit’s fixing
■
■
■
Check if Indoor Unit has not suffered damages by transport. The packaging must be intact. Otherwise, logde
a complaint to transporter.
During removal, take care to the following symbols on packaging.
Concerning the details related to the installation of fixing devices, refer to the following Figures.
For fixing, use bolts with anchors of suitable diameter as regards Unit’s weight.
Fixing devices to be used for ceiling depend on nature of building materials. In case of doubts, please
contact the building firm.
Installation & Service spaces
Install Units at more than 1m from radio and TV appliances, and set power lines and wiring at a suitable
distance from these appliances, to avoid the danger of mutual interferences and electromagnetic noises on
system operation. Sometimes, min. distance of 1m from radio frequency appliances is not sufficient to avoid
the risk of noises on system operation. It is a good rule to use shielded cables.