INS-82
DUAL, TRIPLE, POKER DC Inverter : 4. Installation
Multi Liberty
DC Inverter
4.7 INSTALLATION OF MULTI LIBERTY DC INVERTER OUTDOOR UNITS
4.7 .1 Accessories required for installation
The following accessories must be available for Outdoor Unit’s installation:
No.
Appearance
Description
Quantity
Drain elbow
Rubber pads
Clip
4.7.2 Selection of place & installation position
Place and supporting surface must not amplify vibrations generated by Outdoor Unit.
The supporting surface must be able to bear Outdoor Unit’s weight.
Air outlet must be oriented to 90° as regards prevailing direction of wind.
Noise generated by Outdoor Unit must not disturb the neighbours.
A place where condensate or defrosting water from Outdoor Unit do not disturb people nor causes
damages to objects.
Installation of a concrete bed for Outdoor Unit must be possible.
[The projection of anchor bolts (4 x Ø8mm, or 4 x Ø10mm) for Outdoor Unit’s base, must be of about
20mm as regards concrete bed].
Please keep Outdoor Unit in safety by reinforcing the fixing system, if Outdoor Unit is exposed to
strong wind or it may fall because of earthquakes or exceptional climatic occurrences.
The installation of a snow shelter must be possible, according to climatic recurrent conditions in the
environment.
Sufficient spaces must be kept free for repairing and maintenance of Unit.
Splitting level differences and max. splitting distances that are foreseen for system must be
observed, also by taking into consideration the position of Indoor Units which belong to the system.
A power supply line has to be prepared having such features as to respect the specifications required
by system. The wires of this power line must have a section suitable to the system’s features.
Besides, the power line must be provided of an earth breaker (specific for Inverter appliances) and
of a circuit breaker having a calibration suitable to the system’s power input, that are indicated on
Outdoor Unit’s plate.
4.7.3 Essential dimensions for installation of Multi Liberty DC Inverter Outdoor Units
•
•
•
•
•
•
•
•
•
•
•
Unit: mm
Dimension
Model
HCKU 406 X2
Width
Height (Max.)
Depth
760
590
285
Distance between
holes (1)
Distance between
holes (2)
530
290
HCKU 536 X2
845
695
335
560
340
HCKU 606 X3
845
695
335
560
340
HCKU 806 X3
845
695
335
560
340
HCKU 706 X4
845
695
335
560
340
HCKU 816 X4
895
860
330
590
333
HCKU 1066 X4
990
966
395
624
366