Error Code on Indoor Unit
Outline of malfunction
E 5
• Troubleshooting for Error Codes shown on Display of Multi Liberty HKEU X Indoor Units
Malfunction of temperature sensor T3 (heat
exchanger’s temperature) or temperature
sensor T4 (outdoor air temperature) on
Outdoor Unit.
Malfunction of temperature sensor (broken or in short-circuit) on O.U.