[03-] Ethernet (Only FT-10 FILL EN)
This sub-block includes the parameters related with the Ethernet of FT-10 FILL controller.
[030 5 ] Data Format
0 : No data transfer.
1 : Continuous data output
(Page 72)
2 : Print mode
(Parameter [040]
(Page 32)
3 : BSI command set
(Page 74)
4 : Modbus TCP High-Low
( * )
(Page 91)
5 : Modbus TCP Low-High
( * )
(Page 91)
6 : Fast continuous mode
(Page 73)
( * ) Warning :
Parameter [ 000 ] and [ 010 ] should not be selected Modbus RTU.
[031 001] Device Address
The address of FT-10 FILL will be entered between 01 to 255.
[032 ] IP Address
The IP address will be entered as ”aaa.bbb.ccc.ddd”. Default is “192.168.16.250”.
For changing the IP address, press the <
Tare
> key and enter the first 3 “a” digits of the IP address.
Press <
Enter
> key to access the following “b”, “c” and “d” address entries.
Press the <
> key to access the next parameter.
[033 ] Subnet Mask Address
The IP address will be entered
as ” aaa.bbb.ccc.ddd ”. Default is “255.255.255.000”.
For changing the IP address, press the <
Tare
> key and enter the first 3 “a” digits of the IP address.
Press <
Enter
> key to access the following “b”, “c” and “d” address entries.
Press the <
> key to access the next parameter.
[034 ] Gateway Address
The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default is “192.168.16.253”.
For changing the IP address, press the <
Tare
> key and enter the first 3 “a” digits of the IP address.
Press <
Enter
>
key to access the following “b”, “c” and “d” address entries.
Press the <
> key to access the next parameter.
[035 ] Local Port
The local port will be entered between 00001 to 65535. Default is “502”.
[036 0] Response Speed
0 : Modbus RTU Answer is sent immediately after Request is received.
1 : Modbus RTU Answer is delayed 20 ms after Request is received.
2 : Modbus RTU Answer is delayed 50 ms after Request is received.
This property is very helpful for slow PLC systems