FT-10 Fill Technical Manual, Rev. 2.21, July 2020
Page 95 of 131
42011
R/W
1
Increment
Dec
Description
1
X 1
2
X 2
3
X 5
42100
R/W
1
Filling mode selection
Refer to parameter [500] on page 70
42101
R/W
1
Feeding type
Refer to parameter [501] on page 70
42102
R/W
1
Preact correction factor
Refer to parameter [502] on page 70
42103
R/W
1
Preact correction
frequency
Refer to parameter [503] on page 70
42104
R/W
1
Check delay
Refer to parameter [504] on page 71
42105
R/W
1
Zeroing period
Refer to parameter [505] on page 71
42106
R/W
1
Zeroing delay
Refer to parameter [506] on page 71
42107
R/W
1
Indication at the end of
filling
Refer to parameter [507] on page 71
42108
R/W
1
Feeding check
Refer to parameter [508] on page 71
42109
R/W
1
Filling time
Refer to parameter [509] on page 71
42110
R/W
1
Start Type
Refer to parameter [50A] on page 71
42111
R/W
1
Indication in filling process
Refer to parameter [50B] on page 71
(1) Write this command after writing values to 40031-32 addresses.
Programming steps of frequent use
……
Reading a weight value:
1. Read 40003 (or 40008, 40073),
2. Check D0=0, D1=1and D5=0,
3. If yes, read a weight value (gross, net or tare),
4. If D0=1, check D0 until system ready,
5. If D1=0, check the error code or if D5=1, check the process error messages from 40105.
Zero Calibration procedure:
1. Check the low byte of 40033. it should be decimal '1' to start adjustment.
2. Load the decimal '188' to 40030 to start Zero calibration.
3. Check the low byte of 40033. it is decimal '3' during zero calibration process.
4. The low byte of 40033 changes to decimal '1' at the end of the Zero calibration.
5. If the low byte of 40033 is '9', check the high byte of 40033 to understand the calibration error.
Span Calibration procedure:
1. Check the low byte of 40033. it should be decimal '1' to start adjustment.
2. First load the span value to 40031-32 and then load the decimal '220' to 40030 to start Span
calibration.
3. Check the low byte of 40033. it is decimal '4' during span calibration process.
4. The low byte of 40033 changes to decimal '1' at the end of the Span calibration.
5. If the low byte of 40033 is '9', check the high byte of 40033 to understand the calibration error.