FT-10 Fill Technical Manual, Rev. 2.21, July 2020
Page 90 of 131
[034 ] Gateway Address
The IP address will be entered as ” aaa.bbb.ccc.ddd ”. Default is “192.168.16.253”.
For changing the IP address, press the <
Tare
> key and enter the first 3 “a” digits of the IP address.
Press <
Enter
> key to access the following “b”, “c” and “d” address entries.
Press the <
> key to access the next parameter.
[035 ] Local Port
The local port will be entered between 00001 to 65535. Default is “502”.
[036 0] Response Speed
0 : Modbus RTU Answer is sent immediately after Request is received.
1 : Modbus RTU Answer is delayed 20 msec after Request is received.
2 : Modbus RTU Answer is delayed 50 msec after Request is received.
This property is very helpful for slow PLC systems
13.1 Ethernet Setup
There are 11 parameters for Ethernet network and Ethernet set up is done by IndFace1x (EtherX PC)
software over Local Network Area as described in this section or you can entry from par. [
03-
] blocks. EtherX
PC software is available in CD which is supplied together with the instrument or on internet www.flintec.com.
Host Name
Device name of the instrument.
Default is ‘ ’.
IP Address
Obtain IP address manually.
Default is
‘192.168.16.250’.
Local Port
Ethernet connection port of the instrument.
Default is ‘502’.
Gateway
Network point that acts as an entrance to another network.
Default is ‘192.168.16.253’.
Subnet Mask
Describes IP address can be used in network.
Default i
s ‘255.255.255.0’.
Primary DNS
Obtain primary DNS manually.
Default is ‘208.67.222.222’.
Secondary DNS
Obtain secondary DNS manually.
Default is ‘208.67.220.220’.
Remote Connection
Automatic connection to any device on the network.
Default is ‘Disabled’.
Remote IP:
IP address of the PC or Device to be connected automatically.
Remote Port:
Ethernet connection point of PC or Device to be connected automatically.
Password Ethernet
: Default password is
123456