Proline Promass Q 500 PROFIBUS PA
Electrical connection
Hauser
57
Proline 500 transmitter
Hardware addressing
1.
1
2
3
4
5
6
7
8
128
64
32
16
8
4
2
1
PR
OFIBUS addr
ess
not used
A0029637
Set the desired device address using the DIP switches in the connection compartment.
2.
On
Off
2
3
1
4
A0029633
To switch addressing from software addressing to hardware addressing: set the DIP
switch to
On
.
The change of device address takes effect after 10 seconds. The device is
restarted.
Software addressing
‣
To switch addressing from hardware addressing to software addressing: set DIP switch
No. 4 to
Off
.
The device address configured in the
Device address
effect after 10 seconds. The device is restarted.
7.7
Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection,
Type 4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following
steps after the electrical connection:
1. Check that the housing seals are clean and fitted correctly.
2. Dry, clean or replace the seals if necessary.
3. Tighten all housing screws and screw covers.
4. Firmly tighten the cable glands.