Proline Promass Q 500 PROFIBUS PA
Electrical connection
Hauser
35
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable ⌀ 6 to 12 mm (0.24 to 0.47 in)
• Spring terminals:
Conductor cross-section0.2 to 2.5 mm
2
(24 to 12 AWG)
Connecting cable for sensor - Proline 500 – digital transmitter
Non-hazardous area, Ex Zone 2, Class I, Division 2
Standard cable
A standard cable can be used as the connecting cable.
Standard cable
4 cores (2 pairs); pair-stranded with common shield
Shielding
Tin-plated copper-braid, optical cover ≥ 85 %
Loop resistance
Power supply line (+, –): maximum 10 Ω
Cable length
Maximum 300 m (1
000 ft), see the following table.
Cross-section
Cable length
0.34 mm
2
(AWG 22)
80 m (270 ft)
0.50 mm
2
(AWG 20)
120 m (400 ft)
0.75 mm
2
(AWG 18)
180 m (600 ft)
1.00 mm
2
(AWG 17)
240 m (800 ft)
1.50 mm
2
(AWG 15)
300 m (1
000 ft)
Optionally available connecting cable
Standard cable
2 × 2 × 0.34 mm
2
(AWG 22) PVC cable with common shield (2 pairs, pair-
stranded)
Flame resistance
According to DIN EN 60332-1-2
Oil-resistance
According to DIN EN 60811-2-1
Shielding
Tin-plated copper-braid, optical cover ≥ 85 %
Operating temperature
When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
can move freely: –25 to +105 °C (–13 to +221 °F)
Available cable length
Fixed: 20 m (65 ft); variable: up to maximum 50 m (165 ft)
Hazardous area, Ex Zone 1, Class I, Division 1
Standard cable
A standard cable can be used as the connecting cable.