Proline Promass Q 500 PROFIBUS PA
Commissioning
Hauser
105
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry / User
interface
Factory setting
Select medium
–
Select medium type.
• Liquid
• Gas
Liquid
Select gas type
The
Gas
option is selected in
the
Select medium
parameter.
Select measured gas type.
• Air
• Ammonia NH3
• Argon Ar
• Sulfur hexafluoride
SF6
• Oxygen O2
• Ozone O3
• Nitrogen oxide
NOx
• Nitrogen N2
• Nitrous oxide N2O
• Methane CH4
• Hydrogen H2
• Helium He
• Hydrogen chloride
HCl
• Hydrogen sulfide
H2S
• Ethylene C2H4
• Carbon dioxide
CO2
• Carbon monoxide
CO
• Chlorine Cl2
• Butane C4H10
• Propane C3H8
• Propylene C3H6
• Ethane C2H6
• Others
Methane CH4
Reference sound velocity
In the
Select gas type
parameter, the
Others
option
is selected.
Enter sound velocity of gas at 0
°C (32 °F).
1 to
99
999.9999 m/s
415.0 m/s
Temperature coefficient sound
velocity
The
Others
option is selected
in the
Select gas type
parameter.
Enter temperature coefficient
for the gas sound velocity.
Positive floating-
point number
0 (m/s)/K
Pressure compensation
–
Select pressure compensation
type.
• Off
• Fixed value
• External value
• Current input 1
• Current input 3
Off
Pressure value
The
Fixed value
option is
selected in the
Pressure
compensation
parameter.
Enter process pressure to be
used for pressure correction.
Positive floating-
point number
0 bar
External pressure
The
External value
option is
selected in the
Pressure
compensation
parameter.
Shows the external process
pressure value.
Positive floating-
point number
0 bar
*
Visibility depends on order options or device settings
10.6.4 Configuring communication interface
The
Communication
submenu guides you systematically through all the parameters that
have to be configured for selecting and setting the communication interface.