Commissioning
Proline Promass Q 500 PROFIBUS PA
120
Hauser
Configuring the switch output
Navigation
"Setup" menu → Pulse/frequency/switch output
‣
Pulse/frequency/switch output 1
to n
Operating mode
Terminal number
Signal mode
Switch output function
Assign diagnostic behavior
Assign limit
Assign flow direction check
Assign status
Switch-on value
Switch-off value
Switch-on delay
Switch-off delay
Failure mode
Invert output signal
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Operating mode
–
Define the output as a pulse,
frequency or switch output.
• Pulse
• Frequency
• Switch
Pulse
Terminal number
–
Shows the terminal numbers
used by the PFS output
module.
• Not used
• 24-25 (I/O 2)
–
Signal mode
–
Select the signal mode for the
PFS output.
• Passive
• Active
Passive