63
Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
3.2.8. Setting a wind delay (shades)
When the wind limitation value is exceeded for a drive, the wind alarm is then triggered
for 5 minutes. If the wind value is once again exceeded within this period, the 5-minute
stop time restarts from scratch.
For shades, a delay time can also be set following the wind alarm, during which the
shade automation is blocked. This means that if the shade is in automatic mode before
a wind alarm, the automatic setting remains switched off after the wind alarm. Further
manual operation is however possible again.
You can reach the wind delay time settings by pressing the buttons:
Set the duration of the shade block after a wind alarm using the arrow keys (0-360 min-
utes, default setting: 0 minutes).
Confirm your setting with the
OK
button.
3.2.9. Define automatic reset
Following a manual intervention, the affected drive or unit remains in manual mode,
and automatic operations are switched off. Once the general Automatic Function time
point is reached, drives and units are once again set to Automatic. Alternatively, the
automatic function can be set to reactivate following a manual intervention. The period
for this can be set.
The Automatic Reset prevents drives from being manually operated and then stay in
an unfavourable position (leaving windows accidentally open, or blinds retracted de-
spite the sunlight).
The general Automatic Reset and reset following a manual intervention can be sepa-
rately activated and de-activated in the Automatic functions menu for each drive group
and each unit.
The Automatic Reset function settings can be accessed by pressing the buttons:
General Automatic Reset
Set the time point by selecting the hour and accordingly the minute fields and setting
the time using the arrow buttons. Default setting: 3:00 AM.
Automatik
einstellen
Windverzögerung
System
Allgemeine
Einstellungen
Automatic
Settings
Automatic Reset
System
General
Settings