52
Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
Automatic Reset time and/or period can be set.
System > Automatic Settings > General Settings > Automatic Reset
3.3. Define automatic reset
3.1.8. Automatic heating settings
For connected heatings the following automatic settings can be changed:
•
Indoor sensor to be used for the heating
•
Indoor day temperature
•
Night mode (period) and indoor night temperature
•
Enable/Disable automatic reset
The automatic heating functions can be accessed by pressing the buttons:
Now you can select individual heatings and adjust their settings. For each heating the
following settings can be changed:
Press the button to select the indoor sensor the control system will use for this heating
(Pre-setting: first sensor in the list). For as long as “
No sensor
” is selected, the indoor
sensor will not be taken into account for control of the heating, i.e. no automatic control
will take place.
Confirm your setting with the
OK
button.
Press the button to set the indoor temperature above which the heating will be
switched on during the day. Until an indoor sensor is selected, the automatic heating
is deactivated. Use the arrow buttons to change the value according to your wish. De-
fault setting: 20.0 °C.
Confirm your setting with the
OK
button.
The heating will engage as soon as the temperature drops below the set value and is
shut down again when the temperature is more than 0.5°C above the set value (hyster-
esis).