Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
To change any of the time periods, press
Timer
.
Set timer, page 59
Press the button to set the ventilation levels of the motorised roof ventilators for the
timed ventilation. The button is only active if a ventilation time has been set.
Use the arrow buttons to change the level according to your desire. Default setting:
Level 3.
Confirm your setting with the
OK
button.
Press the button to set the outdoor temperature above which the supply air unit should
remain closed (winter operation). Use the arrow buttons to change the value according
to your wish. Default setting: 1.0 °C.
Confirm your setting with the
OK
button.
Press the button to set the recirculating air function for heat recovery. Recirculation al-
lows heated air from the first area to be distributed in the entire room and so be used
for warming if required. In principle, the recirculation function only starts if the temper-
ature at the ventilator is at least 3° warmer than the indoor temperature.
Select Yes to activate the heat recovery function (with No, the function is switched off).
Use the arrow keys that appear to set the indoor temperature beneath which circula-
tion should take place, and the level at which the ventilator should run.
Default setting: Indoor temperature 10.0°C lower; with level 3.
Confirm your setting with the
OK
button.
Press the button to set the recirculating air function for condensation reduction. Recir-
culation of the air can reduce condensation forming on the window panes.
Select
Yes
to activate the condensation reduction function (with No, the function is
switched off). Using the arrow keys that appear, set the U-value of the glass used (ask
your window manufacturer or conservatory supplier for the value) and the level at
which the ventilator should run. Default setting: U-value 1.0; with Level 3.
Confirm your setting with the
OK
button.
Ventilation Level
Only for WL610/305.
Outdoor Temp
Only for WFL and ventilation units at RF Relay.
Heat Recovery
Only for roof ventilators WL610 and WL305.
Condensation
Only for roof ventilators WL610 and WL305.