30
Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
setting: 5.0 °C. The block is countermanded again when the temperature rises more
than 2.0°C over the pre-set value (hysteresis).
Set the shade
behavior
in the next menu item.
Disable block: If the awning should be deployed to offer shade regardless of the out-
door temperature (for example with internal awnings), press the
Off
button.
Confirm your setting with the
OK
button.
Set the way in which the shade should behave when the outdoor temperature block is
triggered. The button is only active once an outdoor temperature has been set.
Retract: If the shade should retract when the outdoor temperature falls below the set
value, select
Yes
(default setting). The shade is only retracted once the movement de-
lay time has elapsed.
Remain in current position: If the shade should not move when the outdoor tempera-
ture falls below the set value, select
No
. When the rain or wind alarm is triggered, the
shade will be retracted nonetheless (the alarm has priority over blocking temperature).
Confirm your setting with the
OK
button.
Press the button to active or deactivate the frost alarm for this shade. The frost alarm
retracts the sun shade if the outdoor temperature is low and it is raining/snowing at the
same time. This protects external shades from icing and from damage through move-
ment when the rails are iced up.
The conditions for the triggering of the frost alarm (outdoor temperature, period) are
defined in the menu „General Settings“.
System > Automatic Settings > General Settings > Frost Alarm
Adjust frost alarm, page 62
When the frost alarm is triggered, manual operation of the shade is initially blocked.
You can remove the block manually however. To do this select the appropriate shade
in the Manual menu and press the frost alarm button. If the button is shown normally
(black writing), the block has been removed. The block will then be first active for this
drive again if it is reactivated maually or the next time the frost alarm is triggered.
Please note that the shade rails or other mechanical components can remain iced even
when the outdoor temperature has already risen to a relatively high value.
The drive and hangings may be damaged if a firmly frozen
outdoor shading is moved!
Activate: If the sun shade is to be retracted when there is a frost alarm, select
Yes
.
Deactivate: If the sun shade should offer shade regardless of the frost risk (e.g. for in-
ternal awnings), select
No
(default setting).