Automatic settings
Control System KNX WS1000 Color
• Status: 18.04.2016 • Errors excepted. Subject to technical changes.
You can reach the frost alarm settings by pressing the buttons:
First set when the frost alarm should be triggered. Use the arrow keys to adjust the out-
door temperature that must be undercut to trigger the frost alarm (e.g. 2.0°C).
Then set how many hours after precipitation the standby for the frost alarm should be
active (e.g. 5 hrs). Choose the standby period so that all humidity of the previous pre-
cipitation has dried.
Then set the conditions for the end of the frost alarm. Set the outdoor temperature to
be exceeded (e.g. 5.0°C) and the duration for which it should be exceeded (e.g. 5 hrs).
Choose the time period so that ice is completely melted thereafter.
The
Off
button lets you deactivate the frost alarm for all shades and windows.
Confirm your setting with the
OK
button.
3.2.7. Set movement limitations (window)
A movement limitation ensures that a window remains only open a portion at low out-
door temperatures. This prevents the room from cooling too rapidly.
The weather data display (Start screen) then shows “Window movement limitation”
next to the outdoor temperature value. The display can also show “Night-time re-cool-
ing” and “Frost alarm” in turn.
2.1. Weather data display (start screen)
You can set the degree to which the opening is restricted for individual windows in the
automatic functions.
You can reach the movement limitation settings by pressing the buttons:
First define the outdoor temperature below which the window movement range be-
comes limited (e.g. 2.0°C).
You can then set how long the outdoor temperature must remain above the set limit
value, so that the movement limitation is cancelled again (e.g. 8 hours).
The
Off
button lets you deactivate the movement limitation for all windows.
Confirm your setting with the
OK
button.
Automatic
Settings
Frost Alarm
System
General
Settings
Automatic
Settings
Movement Limitation
System
General
Settings