9
InStallatIon anD oPeratIon manual
25-15049-G
October 2021 www.eaton.com
3. About the xDetect Fire Panel System
alarm Confirmation Input from fire alarm routing equipment - Found on Io card
(14-0409) when programmed via xDetectWorks
(option 7 .9 .2 en54 Pt2)
This input, which is monitored using an end of line device, is used for the
confirmation from the fire alarm routing equipment. The confirmation output from the
fire alarm routing equipment must be connected via a 200ohm resistor.
It operates by using the output (e.g. relay) of the fire alarm routing equipment
connecting the 200ohms in parallel with the end of line device (200Ω + diode).
Ensure the polarity of the connections are observed at all times and end of line
device (200Ω + diode) is fitted for correct operation.
output to fire alarm protection equipment - Found on Io card (14-0409) when
programmed via xDetectWorks
(option 7 .10 BS en54-2)
This output, which is fused, and monitored using an end of line device (Eaton
part no. EOLCF3VDS) used for the transmission of the fire signals to controls for
automatic fire protecting equipment (e.g. Door released units etc). It operates by
providing 24 V output to an auxiliary device ( e.g. relay).
It is current limited to 100 mA using a resettable polyswitch ,but load limited to
30 mA. Class change and test conditions do not operate this output. If operated
under a fire alarm condition , this output remains energised until the fire
alarm is reset.
Ensure the polarity of the connections is observed at all times and end of line device
(200 Ω + diode) is fitted for correct operation.
FPe confirmation input from fire protection equipment – found on Io card
(14-0409) when programmed via xDetectWorks
(option 7 .10 .3 en54 Pt2)
This input, which is monitored using an end of line device, is used for the
confirmation from the fire protection equipment. The confirmation output from the
fire alarm routing equipment must be connected via a 200ohm resistor.
It operates by using the output (e.g. relay) of the fire protection equipment
connecting the 200ohms in parallel with the end of line device (200Ω + diode).
Ensure the polarity of the connections are observed at all times and end of line
device (200Ω + diode) is fitted for correct operation.
ote:
n
The confirmation from the fire protection equipment can also be provided by
an MCIM (Micro Single Channel Input Units) connected to one of the
loop cards.