14
InStallatIon anD oPeratIon manual
25-15049-G
October 2021 www.eaton.com
3. About the xDetect Fire Panel System
Transmission path ratings
Recommended Cable
FP200 ≤2.5mm
2
csa
Maximum conductor
resistance @20oC
7.4 Ω/km
Maximum Capacitance
Core-Core
98 nF/km
Loop Card
Number of Inputs/Outputs
1
Input/Output type
loop output
Output voltage
27.24-28.34 V
Input Current Maximum
N/A
Output Current Maximum
600 mA
O/P current limited
1.1 A
Cable length maximum
2 km
Sounder Card
Number of Inputs/Outputs
2
Input/Output type
Spur output
loop output
Output voltage
27.24-28.34 V
27.24-28.34 V
Input Current maximum
N/A
N/A
Output Current maximum
0.75 A per output
0.75 A per output
O/P current limit/trip
3 A
Cable length maximum
0.5 km
Loop 2 km
Gateway Card
Number of Inputs/Outputs
4
Input/Output type
General Fault output FWRE Output
5V Ext.
Battery Input Ethernet Port Printer Port
Output voltage
N/A
20.4-28 V
N/A
Input voltage
30 V
N/A
5 V
Input Current maximum
30 mA
N/A
5 mA
Output Current maximum
N/A
30 mA
N/A
Fuse (resettable PTC)
100 mA
100 mA
N/A
Cable length maximum
2 km
2 km
N/A
IO Card
Number of Inputs/Outputs
5
Input/Output type
Voltage Monitored
Output
Voltage Free
Output
Input
Aux Output
Input voltage
N/A
30 V
30 V
N/A
Output voltage
20.4-28 V
N/A
N/A
20.4-28 V
Input Current maximum
N/A
2 A
60 mA
N/A
Output Current maximum
55 mA
N/A
N/A
250 mA
Fuse (resettable PTC)
100 mA
2.5 A
100 mA
250 mA
Cable length maximum
2 km
2 km
2 km
2 km