22. Supported Languages
Quarterly
Check all previous log book entries and verify that remedial action has been taken.
Carry out the weekly test. Visually examine the batteries and their connections.
Disconnect the mains supply and check that the batteries are capable of supplying
the alarm sounders, by operating a call point.
annual test
As Weekly Test and Quarterly Test above. Additionally test all sensors and call points
and check operation.
every 2-3 years
During the normal servicing cycle check analogue levels of the detectors. If any
are approaching the pre-alarm level then the proprietary cleaning methods can be
adopted. e.g. high pressure air spray.
every 5 years
Replace sealed lead acid batteries.
Remember to update the next ‘Service date’ for the system after the check.
21.3 Non routine
From time to time, the xDetect panel may require non-routine attention, including
special maintenance. Non-routine maintenance includes:
1. A special inspection of an existing system when a new organization takes
over maintenance of the system.
2. Repair of faults or damage.
3. Modification to take account of extensions, alterations or changes
in occupancy.
4. Inspection and test of the system following a fire.
22. Supported Languages
xDetect supports multiple languages, the availibility of which will depend on the
installed language pack(s). English is included as standard - to order additional
languages packs, please contact Eaton.