96
InStallatIon anD oPeratIon manual
25-15049-G
October 2021 www.eaton.com
13. Testing
On exit, the panel shall perform a soft reset, before returning to normal quiescent
operation. A log record for each test event is created, indicating the walk test start,
activation and termination.
13.4 Zone Test
Allows the user to confirm the operation of a zone during fire alarm condition.
The test is accessed through user access 3 (engineer).
1. Select ‘
tests
’ from the main menu
xDetect
0
0
2
0
0
3
Panel 2
19:09
23/8/21
Alarm Count: 5
Evacuate
Event Log
Computer
Reset
Silence/
Resound
Enable/
Disable
View Data
Commissioning
Settings
Tests
2. Select ‘
test Zone
’ from the test menu.
Weekly Test
Panel
LED Test
Walk Test
Test Zone
Loop Analogue
Values
Sound Level
Test
PSU Monitor
Tests
xDetect
0
0
2
0
0
3
Panel 2
19:09
23/8/21
Alarm Count: 5
A screen prompting for zone selection is displayed. Any number of zones may be
placed into test.