InStallatIon anD oPeratIon manual
25-15049-G
October 2021 www.eaton.com
5. Compatible Equipment
Transmission path ratings
Network Card
Number of Inputs/Outputs
3
Input/Output type
RS485
(A, B connections)
Aux Output
Input voltage
0-3.3 V
N/A
Output voltage
0-3.3 V
20.4-28 V
Input Current maximum
28 mA
N/A
Output Current maximum
28 mA
50 mA
Fuse (resettable PTC)
N/A
50 mA
Cable length maximum
2 km
2 km
Zones / Addresses / Fire alarm devices
Maximum Addressable
points per loop circuit
200
Maximum load per loop
600 mA (inputs &
outputs)
Maximum Zones per loop
circuit
200
Maximum Addressable
points per CIE
400 (2 loop panel)
800 (4 loop panel)
Maximum Zones per CIE
256
Maximum Fire alarm devices 100 per loop
Maximum Fire alarm devices
per sounder output
up to 106 (based on
lowest operating
current of RoLP)
Maximum Fire alarm
devices per CIE
up to 262
(2 loop panel)
up to 524
(4 loop panel)
5. Compatible Equipment
For a list of compatible devices please see www.eaton.com/xDetect