12. Commissioning
12. Commissioning
12.1 Commissioning the system using the HMI
The system should be commissioned by a competent person, who has access to
the requirements of the designer (i.e. the system specification). The person should
possess, at least, a basic knowledge and understanding of Section 2 and Section 3
of BS 5839-1:2017 standard.
12.1.1 Auto-Learn
1. From the menu screen and while logged in as Engineer, select
‘
Commissioning
’.
2. Select ‘
auto-learn
’
xDetect
0
0
0
0
0
3