Issue Date: 11/12/2017
Rev:01
Important Warnings
General
✓
Before using the device read this manual carefully. Keep it just in case of necessity.
✓
Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.
✓
Keep the devices away from water and moisture
Service
Do not try to fix the device on your own. Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical
interventions have to be done by technicians of company.
Malfunctions that require technical service
In case of any malfunction or below conditions contact with your authorized service,
✓
When Mains cable or the plug is harmed,
✓
Contact of device with a fluid,
✓
Exposure of rain and water,
✓
Fell down of device or harmed outer cover,
✓
Serious performance fall on the device,
✓
Depending on the instructions stated in manual, if your device not working properly
Contact with your authorized service in such terms.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are
allowed for cleaning
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
Sub Models
TFS-3193R
Conventional Fire Alarm Strobe, Red
TFS-3193W
Conventional Fire Alarm Strobe, White
Technical Features
TFS-3193R
TFS-3193W
Power Input
24VDC
–
28VDC
24VDC
–
28VDC
Alarm Current Consumption
~6 mA ( @24VDC ) 145mW
~6 mA ( @24VDC ) 145mW
Leds
Wide Angle 7 bright LEDs (RED)
Wide Angle 7 bright LEDs
(WHITE)
IP Class
IP21C
IP21C
Operating Temperature Range
-10
C ~ 55
C
-10
C ~ 55
C
Humidity
@ +40°C between %0 to %95
Max
@ +40°C between %0 to %95
Max
Dimensions (mm)
Ø:110mm, h:55mm
Ø:110mm, h:55mm
Housing Material
Red, UL94 fireproof ABS
White, UL94 fireproof ABS
Kullanılan Kablo Kesiti
0.28mm ² ~ 1.5mm ²
0.28mm ² ~ 1.5mm ²
Ağırlık (taban dahil / taban
hariç)
coverage zone
W-2,4-4
Usage Area
Internal indoor use
Terminals
Number 1
To next siren Negative (-)power out
Number 2
Negative (-)power input
Number 3
To next siren Positive (+)power out
Number 4
Positive (+) power input
EN 54-23 Visual Alarm Devices
Mounting and Connection
1.
Remove the head of the siren from the base.
2.
Mount the base part on the wall, using 2 of the 4 markings marked on the base.
Warning:
Do not attempt to remove the electronic board from its plastic case. The electronic board is
closed for your safety. Users should avoid from interference.
TFS-3193
Convensional Fire Alarm Strobe
Installation & Operating Guide