background image

HLogic Security Technology Co., Ltd

www. hstfire .com Document Ref: M7033-04 Issue: 1.7 07/2017// Page 1 of 3

INSTALLATION AND MAINTENANCE INSTRUCTIONS

HB101

Conventional Electric Alarm Bell

BEFORE INSTALLING

NOTICE:

This manual should be left with the owner/user

of this equipment.

SPECIFICATIONS

Voltage ranges: 22vdc to 26vdc (Rated voltage: 24vdc)
Power and current consumption: 0.5W, 18ma@26vdc(maximum)
Number of standard: EN54-3
Sound level

85dB

A

@1M (minimum)

Bell Tone

4500 Hz Continuous

Service Use: Fire alarm, general signaling, burglar alarm
IP ratings: IP21C
Environment type: Type A (indoor)
Input terminal Wire Gauge: 0.28 mm

2

to 1.5 mm

2

Operating Temp.: -10

to +55

Operating Humidity Range: 10% to 93% Relative Humidity ( Non-condensing)
Material of cover: Aluminum
Dimension: 150mm×55mm

D*H)

Weight: Net Weight 380g, Gross Weight 420g

Structure

Label

The name of component

A1

Cover of bell

A2

Label of front

A3

Screw of fixed

B1

Mounting bracket

B2

Label on bracket

B3

Enclosure

©





Figure1: Fire Alarm Bell

Figure2: The Structure Of Fire Alarm Bell

A1

A2

A3

B1

B2

B3

Front size

Back size