Troubleshooting
SiENBE04-925_A
76
Service Diagnosis
4.2
Indoor Unit PCB Abnormality
Remote Control
Display
A1
Method of
Malfunction
Detection
Evaluation of zero-cross detection of power supply by the indoor unit PCB.
Malfunction
Decision
Conditions
There is no zero-cross detection in approximately 10 seconds.
Supposed
Causes
Wrong models interconnected
Defective indoor unit PCB
Disconnection of connector
Troubleshooting
Note:
Check the following connector.
Check the combination of the
indoor and outdoor unit.
OK?
Check the connection of
connectors (See Note.).
Correct the connection.
OK?
Error repeats?
YES
NO
NO
YES
NO
YES
(R11704)
Caution
* To secure the connection,
once disconnect the connector
and then reconnect it.
Match the compatible
models.
Replace the indoor unit
PCB (1).
Replace the indoor unit
PCB (1).
Completed.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Model Type
Connector
Wall Mounted Type
Terminal board ~ Control PCB
SIENBE04-925_A_FRONT.pdf 91
24/02/2011 13:53:56
Содержание RXL25G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents ...
Страница 14: ...Introduction SiENBE04 925_A xii ...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications ...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...