Control Specification
SiENBE04-925_A
48
Function and Control
3.13 Forced Operation Mode
Outline
Forced operation mode includes only forced cooling.
Detail
3.14 Standby Electricity Saving
20/25 Class Only
This function turns power supply OFF to the outdoor unit and sets the indoor unit into energy-
saving mode, thus reducing the power consumption of the air conditioner.
For 20 class models, field setting is required for turning ON the function.
Refer to “Standby Electricity Saving” on page 269 for detail.
Item
Forced Cooling
Conditions
1) The outdoor unit is not abnormal and
not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced operation is allowed when
the above both conditions are met.
Start
1) Press the forced operation ON/OFF
button (SW1) on the indoor unit for 5
seconds.
2) Press the forced operation ON/OFF
button (SW1) on the outdoor unit.
Command
frequency
RXL20G2V1B: 68 Hz
RXL20G2V1B9: 58 Hz
RXL25G2V1B: 47 Hz
RXL35G2V1B: 66 Hz
End
1) The operation ends automatically
after 15 minutes.
2) Press the forced operation ON/OFF
button (SW1) on the indoor unit again.
3) Press the ON/OFF button on the
remote control.
4) Press the forced operation ON/OFF
button (SW1) on the outdoor unit.
Others
The protection functions are prior to all
others in the forced operation.
SIENBE04-925_A_FRONT.pdf 62
24/02/2011 13:53:53
Содержание RXL25G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents ...
Страница 14: ...Introduction SiENBE04 925_A xii ...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications ...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...