SiENBE04-925_A
Troubleshooting
Service Diagnosis
93
Troubleshooting
Check No.04
Refer to P.118
Check No.06
Refer to P.120
Check No.11
Refer to P.122
(R7141)
Caution
NG
• Discharge pipe thermistor
• Outdoor heat exchanger thermistor
• Outdoor temperature thermistor
• Refrigerant shortage
• Four way valve
• Water mixed
• Stop valve
OK
OK
OK
NG
NG
Check No. 06
Check the thermistors.
Check No. 11
Check the refrigerant line.
Check No. 04
Check the electronic
expansion valve.
Replace the defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
SIENBE04-925_A_FRONT.pdf 108
24/02/2011 13:53:56