Troubleshooting
Service Diagnosis
115
4.25 Low-voltage Detection or Over-voltage Detection
Remote Control
Display
U2
Method of
Malfunction
Detection
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Malfunction
Decision
Conditions
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 150 ~ 180 V (depending on
the model).
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
(The voltage is over 400 V.)
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes (35 class: 5 minutes) without any
other error
Supposed
Causes
Supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Layer short inside the fan motor winding
SIENBE04-925_A_FRONT.pdf 130
24/02/2011 13:53:57
Содержание RXL25G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents ...
Страница 14: ...Introduction SiENBE04 925_A xii ...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications ...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...