Outdoor Unit - RXL25G2V1B
SiENBE04-925_A
238
Removal Procedure
4
Remove the protection
bushing.
5
Remove the 2 nuts of
the compressor.
Warning
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Warning
Since it may happen that the
refrigerant oil in the
compressor catches fire,
prepare wet cloth so as to
extinguish fire immediately.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Before working, make
sure that the refrigerant
gas is empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
6
Heat up the brazed part
of the discharge side
and disconnect.
7
Heat up the brazed part
of the suction side and
disconnect.
Step
Procedure
Points
(R8199)
Protection bushing
U
W
V
(R0265)
(R8201)
SIENBE04-925_A_FRONT.pdf 253
24/02/2011 13:54:16
Содержание RXL25G2V1B
Страница 8: ...SiENBE04 925_A vi Table of Contents ...
Страница 14: ...Introduction SiENBE04 925_A xii ...
Страница 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 20: ...Specifications SiENBE04 925_A 6 Specifications ...
Страница 186: ...SiENBE04 925_A Outdoor Unit RXL20G2V1B Removal Procedure 171 4 Feature of the thermistors Step Procedure Points R9356 ...