![Daikin RXL25G2V1B Скачать руководство пользователя страница 170](http://html.mh-extra.com/html/daikin/rxl25g2v1b/rxl25g2v1b_service-manual_501970170.webp)
SiENBE04-925_A
Indoor Unit
Removal Procedure
155
2
Loosen the lock screw
and remove the fan
rotor.
When reassembling the fan
rotor, provide as much as
5 mm of play between the
side face of the rotor and the
bottom frame.
(1) Insert the fan motor with
approx. 5 mm left.
(2) Tighten the screw until it
stops. Then turn the screw
in one scroll.
(3) Move the fan rotor and
confirm the fan motor and
the fan rotor are installed
appropriately.
(4) Tighten the screw
completely if appropriate.
(5) If not appropriate, go back to
(1).
3
Press the bearing
ASSY from outside.
4
Remove the bearing.
Step
Procedure
Points
(R8120)
Lock screw
Fan motor
(R2808)
Side face of rotor
Side face of
bottom frame
5 mm
(R9582)
(R8121)
(R8122)
SIENBE04-925_A_FRONT.pdf 170