Field Settings
SiENBE04-925_A
268
Trial Operation and Field Settings
2. Field Settings
2.1
When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, 1 of the 2 pairs of indoor unit and infrared remote
control can be set for different address.
Both the indoor unit PCB and the infrared remote control need alteration.
Indoor Unit PCB
(1) Remove the front grille. (2 screws)
(2) Remove the electrical box. (1 screw)
(3) Remove the shield plate. (4 hooks)
(4) Cut the address setting jumper JA on the control PCB.
Infrared Remote
Control
(1) Remove the cover and take it off.
(2) Cut the address setting jumper J4.
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT
2
(R12216)
J4
ADDRESS
EXIST
1
CUT
2
J4
(R12235)
SIENBE04-925_A_FRONT.pdf 283
24/02/2011 13:54:20